EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0
page 1 of 114
c-pro 3 NODE kilo AHU
PROGRAMMABLE CONTROLLERS FOR AIR
HANDLING UNITS
ENGLISH
APPLICATION MANUAL version 1.0
CODE 144CP3NKAHE104
Vue de la page 0
1 2 3 4 5 6 ... 113 114

Résumé du contenu

Page 1 - HANDLING UNITS

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 1 of 114 c-pro 3 NODE kilo AHU PROGRAMMABLE CONTROLLERS FOR AIR HANDLING UNI

Page 2 - Important

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 10 of 114 3 User interface For the application there is an only interface:

Page 3

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 100 of 114 8.2 MQTT As default, the MQTT functionality is disabled. To enabl

Page 4

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 101 of 114 9 List of Modbus® variables This section will be updated with the

Page 5

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 102 of 114 0x0286 647 out_Humidifier 0.00 0.00 100.00 R/W 0x0287 64

Page 6 - 1 GENERALITIES

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 103 of 114 0x0604 1541 F2_Monday_h2 ( Low ) 00:00:00 00:00:00 23:59:59

Page 7 - 2 Dimensions

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 104 of 114 0x062C 1581 F3_Friday_h3 ( High ) 0x062D 1582

Page 8

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 105 of 114 0x0654 1621 PM90_LastMaintainDATE ( Low ) 01/01/2008 00:00:01

Page 9

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 106 of 114 0x067E 1663 Pb01_Temperature_Diff_Valve 10.0 0.0 36.0 R/W

Page 10 - 3 User interface

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 107 of 114 0x06A8 1705 PP02_SetON_Pump 5.00 1.00 90.00 R/W 0x06A9 1

Page 11

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 108 of 114 0x06D2 1747 PH14_Modbus_StopBit 0 0 1 R/W 0x06D3 1748 P

Page 12 - 4 List of pages

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 109 of 114 0x0701 1794 PH80_Select_TypeAO_coil1 3 1 3 R/W 0x0702 17

Page 13 - 4.2 Main page

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 11 of 114 3.2 Display that can be viewed from the Vroom interface From the

Page 14 - 4.2.2 (TIME BANDS) screen

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 110 of 114 0x072E 1839 PA35_ThermalResistorAlarm_Delay 2 0 999 R/W 0

Page 15 - 4.2.3 Fans Screen

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 111 of 114 0x0756 1879 HB01[7] 0 0 18 R/W 0x0757 1880 HB01[8] 0

Page 16

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 112 of 114 0x0780 1921 PE01_Eth_IP_Address (IP3.IP4) R/W 0x0781

Page 17

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 113 of 114 c-pro 3 NODE kilo AHU Application manual ver. 1.0 PT - 47/14 Code

Page 18 - 4.4 User menu

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 114 of 114 EVCO S.p.A. Via Feltre 81, 3

Page 19 - 4.6 Installation menu

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 12 of 114 4 List of pages This chapter describes the main pages and menus fe

Page 20

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 13 of 114 4.1 Password A level is assigned to every menu that determines the

Page 21 - 4.8 Alarms menu

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 14 of 114 1) Summer / winter/ alarm 2) Time band T1/ T2/ T3/ Holiday /

Page 22 - 5 Parameter list

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 15 of 114 4.2.3 Fans Screen The following can be displayed in this scree

Page 23

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 16 of 114 4.2.6 Direct expansion coil regulation status screen The regul

Page 24

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 17 of 114 4.2.9 Status screen of the damper for air circulation The air c

Page 25

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 18 of 114 4.2.12 Sensors status screen The status of the sensors is displa

Page 26 - 0.0 -20.0 20.0 °C UT

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 19 of 114 4.5 Maintenance menu The Maintenance menu is a Level 2 menu

Page 27 - 0.0 -20.0 20.0 °C UT

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 2 of 114 Important Important Read this document thoroughly before installatio

Page 28

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 20 of 114 In the CONTROL Menu you can set/view parameters for various specifi

Page 29

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 21 of 114 4.7 RTC menu This menu contains the functionality of the systems R

Page 30

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 22 of 114 5 Parameter list The parameters managed by the application are li

Page 31

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 23 of 114 5.1 List of configuration parameters Note: Once the machine paramet

Page 32

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 24 of 114 Tuesday hour band 3 0 00:00:00 23:59:59 TB Wednesday type b

Page 33

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 25 of 114 Friday type band 1 0: Disable 1: T1 2: T2 3: T3 0 0 3 TB

Page 34

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 26 of 114 Sunday hour band 1 0 00:00:00 23:59:59 TB Sunday type band

Page 35

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 27 of 114 OE01 Economy Offset 0.0 -20.0 20.0 °C UT PSd1 Password fo

Page 36

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 28 of 114 PC05 Enable cycles for air quality sensors for ambient temperatur

Page 37

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 29 of 114 PF17 Max. temperature of limitation 40.0 -15.0 70.0 °C IS-F

Page 38

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 3 of 114 Index 1 GENERALITIES ...

Page 39

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 30 of 114 Pb24 Differential for midseason control 3.0 0.0 10.0 °C IS-B

Page 40

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 31 of 114 PU19 Neutral zone management winter dehumidification 6 0 100

Page 41

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 32 of 114 PS21: Differential – Air Quality Control 100 0 2000 ppm IS-SE

Page 42

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 33 of 114 PA21 Pressure switch alarm delay (heat recovery device) 30 0

Page 43

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 34 of 114 PH13 ModBus parity (0=none, 1=Odd, 2=Even) 2 0 2 - IS-M PH1

Page 44

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 35 of 114 PH26 Enable variation Set Point as Supervisor NO (0) NO (0) YES

Page 45 - 6 Regulations

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 36 of 114 PH44 Type of expelled air temperature sensor 0: PTC 1: NTC 2: PT100

Page 46 - 6.3 Unit type

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 37 of 114 PH55 Logic for Digital inputs used for coil 2 pump alarm NO

Page 47 - 6.4 Electric connections

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 38 of 114 PH80 Type of coil 1 AO sensor 1=0-20mA 2=4-20mA 3=0-10V 3 1 3 -

Page 48

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 39 of 114 PSd3 Password Installation Operator Level (3) 0 -999 9999 -

Page 49 - 6.5 Electric connections

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 4 of 114 6.8 Plant set-up ...

Page 50

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 40 of 114 HA00 Use of temperature and environment humidity probes 0: none

Page 51 - 6.6 Operating mode control

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 41 of 114 HB12 Assignment DI12 (see table par. 4.1.2) 0 0 18 - IS-DI HB

Page 52 - 6.8 Plant set-up

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 42 of 114 5.1.1 AI parameters I/O table AI1-2-3-7-8-9 Code Description

Page 53

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 43 of 114 10 General alarm input 11 Chiller unit defrosting 12 Flow fan

Page 54

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 44 of 114 5.1.3 DO parameters I/O table DO Code Description Notes

Page 55

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 45 of 114 6 Regulations 6.1 Machine status Several procedures exist for swi

Page 56

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 46 of 114 6.2 Alarm OFF status When the machine is turned on an additional

Page 57

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 47 of 114 6.4 Electric connections 6.4.1 Machine electric connections w

Page 58

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 48 of 114 c-pro 3 NODE kilo AHU - Double flow unit with ON-OFF ventilation (W

Page 59

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 49 of 114 6.5 Electric connections 6.5.1 Machine electric connections wit

Page 60

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 5 of 114 6.17.2 Heat recovery devices with double coil ...

Page 61 - FLOW ON-OFF:

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 50 of 114 c-pro 3 NODE kilo AHU – Single flow unit with ON-OFF ventilation (W

Page 62

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 51 of 114 6.6 Operating mode control The operating modes can assume the foll

Page 63

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 52 of 114 6.7 Setting the RTC When the power supply is disconnected from

Page 64

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 53 of 114 Screen from where it is possible to set the SETUP of the fans, acti

Page 65

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 54 of 114 Screen from which the coil type can be configured (Coil 1 type),

Page 66

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 55 of 114 Screen from where it is possible to configure coil 2, selecting wit

Page 67

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 56 of 114 6.9 Table of types of configurable machines Once the parameters ar

Page 68 - 6.10 Fans

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 57 of 114 43 Double flow Modulating Water (H/C) Electrical 2st 44 Double flow

Page 69

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 58 of 114 The following table shows the machines with configurable drive type

Page 70

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 59 of 114 95 Single flow 3 Speed Water (H/C) Electrical mod 96 Single flow

Page 71

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 6 of 114 1 GENERALITIES 1.1 Description c-pro 3 NODE kilo AHU is a c

Page 72

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 60 of 114 141 Single flow Modulating DX (C,2st) Electrical 2st 142 Single fl

Page 73 - 6.10.10 Fan alarm inputs

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 61 of 114 The following table shows the possible configurations of I/

Page 74 - 6.11 Main controls

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 62 of 114 The following table shows the possible configurations of I/O

Page 75

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 63 of 114 The following table shows the possible configurations of I/O by def

Page 76

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 64 of 114 The following table shows the possible configurations of I/O by de

Page 77 - 6.13 Post-heating

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 65 of 114 The following table shows the possible configurations of I/O by de

Page 78 - 6.13.4 Resistance in summer

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 66 of 114 Code 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 1

Page 79 - 6.14 Dehumidification

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 67 of 114 DI8 Disab. Disab. Disab. Disab. Disab. Disab. Disab. Disab. Disab.

Page 80

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 68 of 114 6.10 Fans The air handling unit can control two fans, one suppl

Page 81

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 69 of 114 SEtH: Set OFF T. room PF02: ON WINTER operating mode 6.

Page 82 - 6.15 Humidification

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 7 of 114 2 Dimensions 2.1 Dimensions controller 8 DIN modules; dimensions a

Page 83

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 70 of 114 PF01: control mode fans PF02: control band PF03: Minimum fan speed

Page 84 - 6.16 Dampers

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 71 of 114 6.10.6 Static Pressure control When a discharge air static pr

Page 85 - Outdoor air dampers

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 72 of 114 6.10.7 Minimum/Maximum discharge temperature When the discharge te

Page 86 - 6.16.6 Damper command

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 73 of 114 6.10.9 Fan status Below are the different operating modes in which

Page 87 - 6.17 Heat recovery devices

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 74 of 114 6.11 Main controls The controller controls both temperature and hu

Page 88

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 75 of 114 6.12 Cooling and heating controls When the primary control is base

Page 89

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 76 of 114 6.12.2 Modulating valve control In order to utilize only a p

Page 90 - 6.18 Heating/cooling pumps

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 77 of 114 1st heating element Pb01 x 2 2nd heating element Set Point - Supply

Page 91 - 6.18.4 Pump alarm inputs

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 78 of 114 6.13.3 Post-heating resistors modulating To use the modulating re

Page 92 - 6.19.2 Primary control

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 79 of 114 6.14 Dehumidification In order to adjust the comfort of the room i

Page 93 - 6.20 Management (various)

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 8 of 114 2.3 Installation remote user interface By panel. By wall (in fl

Page 94 - 6.21 Time schedule

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 80 of 114 6.14.2 Limit regulation of dehumidification When there is an a

Page 95 - 7 Diagnostics

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 81 of 114 Example 3 Dehumidification request = 80% Dehumidification lim

Page 96 - 7.2 Table of Alarms

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 82 of 114 6.15 Humidification To adjust the comfort of the room it is necess

Page 97 - 7.3 Alarm relay

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 83 of 114 6.15.3 Step of modulating humidifier with On / Off To use the modu

Page 98 - 7.4 Alarms log

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 84 of 114 6.15.5 Maximum humidity protection A maximum humidity hygrostat ca

Page 99 - 8.1 Web Server

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 85 of 114 6.16.3 Enabling Free-Cooling / Free-Heating in temperature The fr

Page 100 - 8.3 ModBus TCP/IP

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 86 of 114 WINTER operation/HEATING: Free-Heating Note: if one of

Page 101 - 9 List of Modbus® variables

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 87 of 114 Note: each time the unit is in ON status (for turning on the card,

Page 102

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 88 of 114 6.17.1 Heat recovery devices at cross flow In order to utilize th

Page 103

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 89 of 114 6.17.2 Heat recovery devices with double coil In order to utilize

Page 104

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 9 of 114 By wall (in CPVW00 wall mounting support).

Page 105

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 90 of 114 Note: the outdoor air temperature sensor must also be enabled (P

Page 106

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 91 of 114 When the control ramp exceeds PP02 the pump will activate; when it

Page 107

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 92 of 114 6.19 Unit with single heating-cooling coil (seasonal) In this ty

Page 108

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 93 of 114 6.20 Management (various) 6.20.1 Single or distinct set point It

Page 109

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 94 of 114 6.20.3 Variation set point from supervisor The program provides th

Page 110

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 95 of 114 7 Diagnostics The application is capable of managing a whole seri

Page 111

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 96 of 114 7.2 Table of Alarms The following is a list of all the alarms

Page 112

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 97 of 114 or disconnected which the sensor is dependent AL28 I/O configurat

Page 113

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 98 of 114 7.4 Alarms log The controller stores in a non-volatile memory th

Page 114

EVCO S.p.A. c-pro 3 NODE kilo AHU | Application manual ver. 1.0 page 99 of 114 8 Ethernet services configuration All the settings about network p